Capacity t=77°F (25°C) | 20 hour rate (13.27A, 10.8V) | 265.4 Ah |
10 hour rate ((25.0A, 10.8V) | 250.0 Ah |
5 hour rate (48.65A, 10.5V) | 243.3 Ah |
1 hour rate (162.9A,10.5V) | 162.9 Ah |
Internal Resistance | Full Charged Battary 77°F (25°C) | <=3.5 mΩ |
Capacity Affected by temperature 20h rate | 104°F (40°C) | 102% |
77°F (25°C) | 100% |
32°F (0°C) | 85% |
5°F (-15°C) | 65% |
Self-Discharge 68°F (20°C) (Capacity after) | 2% of capacity declined per month at (25 ) |
Terminal | T16 |
Charge (Constant Voltage, 25°C) | Cycle | 14.4-14.6V (-30 mV/°C) max. current: 75.0A |
Float | 13.6-13.8V (-20 mV/°C) |